Victron MultiPlus-II 48/5000/70-95 120V (UL 1741) Inverter | PMP482505120

Only 3 left in stock
SKU PMP482505120
$1,540.20

Compatible accessories & add-ons

Still have questions?

We're here to help! Give us a call and talk with a US-based technical expert.

Give us a call1-888-501-1846
Victron MultiPlus-II 48/5000/70-95 120V (UL 1741) Inverter | PMP482505120 – view 1 of 4
1/4
Hover to zoom

5000VA · 70A charger · 95A transfer switch · UL 1741

Victron MultiPlus-II 48/5000/70-95 120V (UL 1741) Inverter | PMP482505120

The UL 1741-listed 48V 120V MultiPlus-II: 5,000VA pure sine wave output, 70A battery charging, a 95A AC transfer switch, PowerAssist, and scalable VE.Bus networking.

The Victron MultiPlus-II 48/5000/70-95 120V (UL 1741), part PMP482505120, is the UL 1741 and CSA C22.2 listed version of Victron’s 5kVA 48V MultiPlus-II for North American systems. It combines a 5,000VA pure sine wave inverter with 4,000W continuous output at 25°C, a 70A adaptive charger, and a 95A transfer switch in one programmable 48V power hub for off-grid homes, backup power, and large marine and RV systems.

48V
Battery system
5,000VA
Pure sine inverter
4,000W
Continuous at 25°C
70A
Battery charger
95A
Transfer switch
UL 1741
Listed model

Built for professional 48V power systems

Genuine VictronPart PMP482505120
UL 1741 listedPlus CSA C22.2 No. 107.1
PowerAssistSupplements limited AC input
Dual AC outputsCritical and source-only loads
VE.Bus scalableParallel and split-phase capable
5-year warrantyVictron standard coverage

The Heavy-Duty Power Hub: Decoding 48/5000/70-95

Inverter, charger, and high-current transfer switch in one integrated platform.

The model name tells you what you are getting: a native 48V battery platform, a 5,000VA inverter stage, up to 70A of DC charging, and a 95A AC transfer switch. The combination suits systems with heavy AC loads and substantial shore, grid, or generator input, where a lower-current transfer stage would become the bottleneck.

5,000VA Pure Sine Wave Inverter

The inverter delivers 4,000W continuous at 25°C, 3,700W at 40°C, 3,000W at 65°C, and 9,000W peak power. Its clean 120V sine wave output supports sensitive electronics and heavy household-style loads when the battery bank, wiring, protection, and ventilation are correctly engineered.

The 95A Transfer-Switch Advantage

A 95A transfer stage can pass a large 120V generator, shore, or grid source through the inverter/charger without a 50A internal transfer limit. The installation still needs correctly sized upstream and downstream breakers, conductors, grounding, and code-compliant distribution.

70A Smart Battery Charger

When external AC is available, the MultiPlus-II becomes a high-output 48V battery charger. Charge voltages, current limits, and algorithms are configurable, so the unit can be commissioned for the exact Epoch battery, managed BMS, and system design.

UL 1741 Listed for North American Installations

What the listing covers, and what to confirm before a grid-connected design.

PMP482505120 is the version of the MultiPlus-II 48/5000/70-95 120V that Victron lists to UL 1741 and CSA C22.2 No. 107.1. Many inspectors and authorities having jurisdiction look for this listing on inverter/chargers in permitted off-grid, backup, and energy-storage installations.

UL 1741 is not the same as UL 1741 SA or SB grid-support certification. Before using any inverter/charger in a grid-interactive or export application, confirm the exact certifications your utility and your authority having jurisdiction require.

Advanced Victron Energy Management

PowerAssist, intelligent load separation, and fast backup transfer.

PowerControl first reduces battery charging to keep the configured AC source within its current limit. If the connected loads still need more power, PowerAssist supplements the AC source with energy from the battery, then uses spare source capacity to recharge when demand falls.

AC-Out-1 backs up critical loads and transfers to inverter power in less than 20ms. AC-Out-2 is reserved for loads that should run only while shore, generator, or grid power is present, helping keep water heaters and other non-critical loads from draining the battery bank.

Scalable: Parallel, Split Phase, and Three Phase

Grow the power platform as system requirements expand.

Two matching units can be configured through VE.Bus to provide 120/240V split-phase power, up to six units can operate in parallel for more inverter and charging capacity, and three matching units can form a three-phase system.

Multi-unit systems need matching models, compatible firmware, correct VE.Bus configuration, and professionally engineered protection.

Compatible applications

Heavy-duty 48V off-grid, backup, marine, and vehicle systems.

  • ✓Large 48V off-grid homes, cabins, workshops, and energy-storage systems.
  • ✓Permitted installations where the inspector or authority having jurisdiction requires a UL 1741 listing.
  • ✓Home and small-business backup power with fast transfer for critical loads.
  • ✓Heavy-duty RV, motorhome, bus, and professional vehicle electrical systems.
  • ✓Marine and yacht systems with a protected, dry inverter compartment.
  • ✓Generator-backed installations that need PowerControl and PowerAssist.
  • ✓Supported 120/240V split-phase systems using two matching units.
  • ✓GX-connected systems using Cerbo GX, Ekrano GX, and the VRM portal.

Inverter/charger features

High-output conversion, intelligent transfer, and connected-system control.

5,000VA pure sine wave inverterClean 120V AC power for sensitive electronics and heavy household-style loads.
4,000W continuous at 25°C3,700W at 40°C and 3,000W at 65°C, subject to installation and cooling conditions.
9,000W peak powerHandles short-duration startup and surge demands within the inverter’s documented limits.
95A transfer switchPasses high-current AC input from a properly protected grid, shore, or generator source.
70A adaptive chargerRecharges a compatible 48V battery bank from AC input using configurable charge settings.
PowerControl and PowerAssistPrevents overload of the configured AC source and supplements limited input with battery power.
Two AC outputsSeparates inverter-backed critical loads from loads that should run only on external AC.
Fast UPS transferTransfers AC-Out-1 to inverter power in less than 20ms when the AC source is lost.
UL 1741 and CSA listingListed to UL 1741 and CSA C22.2 No. 107.1 for North American installations.
96% maximum efficiencyHigh conversion efficiency helps reduce losses in a well-designed 48V system.
Search and AES modesReduce idle consumption when loads are low or absent.
VE.Bus networkingSupports configuration, monitoring, parallel operation, split phase, and system integration.

Recommended Victron accessories

Configuration, communication, monitoring, and sensing components.

✓Victron MK3-USB Interface for commissioning, configuration, and firmware updates.
✓Genuine Victron RJ45 UTP cable for VE.Bus connections.
✓Cerbo GX or Ekrano GX for system integration and VRM remote monitoring.
✓VE.Bus Smart Dongle for local Bluetooth monitoring and selected controls.
✓Optional external AC current sensor for PowerControl, PowerAssist, and ESS functions.
✓Victron battery temperature sensor for temperature-compensated charging where required.

Technical specifications

Part-specific performance, connectivity, mechanical details, and installation values.

Product identification
ManufacturerVictron Energy
ProductMultiPlus-II 48/5000/70-95 120V (UL 1741) inverter/charger
Part numberPMP482505120
Core functionsPure sine wave inverter, adaptive battery charger, transfer switch, PowerControl and PowerAssist
CertificationUL 1741 and CSA C22.2 No. 107.1
Warranty5-year standard Victron warranty
Inverter
Battery-system voltage48V nominal
DC input voltage range38–66VDC
AC output120VAC ±2%, 60Hz ±0.1%
Continuous apparent power at 25°C5,000VA
Continuous real power at 25°C4,000W
Continuous power at 40°C3,700W
Continuous power at 65°C3,000W
Peak power9,000W
Maximum efficiency96%
No-load power15W
No-load power in AES mode10W
No-load power in Search mode3W
AC input and transfer
AC input voltage range90–140VAC
Maximum AC input current95A
Transfer-switch rating95A
AC-Out-1Inverter-backed no-break output
AC-Out-2Auxiliary output; live only while external AC input is present
Transfer time on AC-Out-1Less than 20ms
PowerControl and PowerAssistYes
Battery charger
Maximum battery charge current70A
Default absorption voltage57.6V
Default float voltage55.2V
Default storage voltage52.8V
Battery temperature sensingSupported
Lithium configurationProgram to the exact battery/BMS manufacturer requirements before operation
Communication and control
VE.BusTwo RJ45 sockets for configuration, monitoring, parallel/split-phase operation, and integration
Programmable relayYes
External AC current sensorOptional
GX and VRM integrationSupported through a Cerbo GX, Ekrano GX, or compatible GX product
Bluetooth optionVE.Bus Smart Dongle sold separately
Computer configurationMK3-USB interface and RJ45 UTP cable sold separately
Scalability
Parallel operationUp to six units, subject to Victron system-design requirements
Split-phase operation120/240V with two matching units in documented configurations
Three-phase operationThree matching units in documented configurations
System requirementMatching models, compatible firmware, correct VE.Bus configuration, and engineered protection
Mechanical and environmental
EnclosureSteel, Victron blue RAL 5012
Protection categoryIP22; dry, ventilated indoor or protected installation required
Operating temperature-40°C to +65°C / -40°F to 149°F, fan-assisted cooling
Dimensions676 × 329 × 164mm / 26.6 × 13.0 × 6.5in
Weight32kg / approximately 70 lb
Victron installation table — 48/5000/70
Recommended DC fuse200A
DC cable, 0–5m runAWG 2/0 positive and negative
DC cable, 5–10m runAWG 4/0 positive and negative
AC-in protection95A
ImportantFollow the current manual, local code, conductor temperature rating, cable type, routing, and authority requirements
Model-specific compliance note
ListingPMP482505120 is Victron’s UL 1741 version of the MultiPlus-II 48/5000/70-95 120V
Related partPMP482505300 is the 120V 50/60Hz variant of the same model family
Grid interconnectionUL 1741 is not UL 1741 SA/SB; confirm utility and AHJ requirements for any grid-interactive design

Commission for the exact battery and power system

Factory settings are not a substitute for system-specific engineering.

Program the battery charge profile, current limits, AC input limit, ground-relay behavior, BMS interfaces, and operating mode for the exact installation. Use an MK3-USB interface or a supported GX or remote workflow, follow the battery manufacturer’s settings, and verify the completed system before energizing loads.

Frequently asked questions

Victron MultiPlus-II 48/5000/70-95 (UL 1741) FAQs

Common questions about the UL 1741 listing, transfer current, split phase, lithium charging, wiring, and monitoring.

What do the numbers 48/5000/70-95 mean?

48 means the unit is designed for a nominal 48V battery system; 5000 is the 5,000VA inverter rating, with 4,000W continuous output at 25°C; 70 is the maximum DC battery charge current in amps; and 95 is the AC transfer-switch and maximum AC input rating in amps.

What does the UL 1741 listing mean for my installation?

PMP482505120 is Victron’s version of this model listed to UL 1741 and CSA C22.2 No. 107.1. Many authorities having jurisdiction look for this listing on inverter/chargers in permitted off-grid, backup, and energy-storage installations. It is not the same as UL 1741 SA or SB grid-support certification, so confirm your utility’s and inspector’s requirements before any grid-interactive design.

How is PMP482505120 different from PMP482505300?

Both are MultiPlus-II 48/5000/70-95 120V inverter/chargers with a 5,000VA inverter, 70A charger, and 95A transfer switch. Victron identifies PMP482505120 as the UL 1741 version and PMP482505300 as the 120V 50/60Hz variant. Choose the UL 1741 model when your installation, permit, or inspector requires that listing.

Why would I choose the 95A transfer-switch version?

The 95A transfer switch lets the unit pass a substantially larger 120V shore, generator, or grid source than a 50A model. It suits heavy-duty systems where the upstream source and downstream distribution are designed for that current. Proper breakers, conductors, grounding, and local-code compliance are still required.

Does one MultiPlus-II provide 120V or 240V output?

One unit provides 120V AC. Two identical units configured through VE.Bus can create a supported 120/240V split-phase system. Parallel and split-phase systems must use matching models and firmware and should be commissioned by a qualified installer using Victron’s current guidance.

What DC fuse and battery cable size does Victron recommend?

Victron’s 120V manual lists a 200A DC fuse for the 48/5000/70 model, AWG 2/0 positive and negative cables for runs from 0–5m, and AWG 4/0 for runs from 5–10m. Local code, ambient temperature, cable construction, routing, and the actual run length may require different sizing.

What is the difference between AC-Out-1 and AC-Out-2?

AC-Out-1 is the inverter-backed no-break output: if the AC source fails, the inverter takes over in less than 20ms. AC-Out-2 is for loads that should run only while shore, generator, or grid power is present; it disconnects on battery operation and reconnects after the AC source is back.

Can the 70A charger be configured for Epoch LiFePO4 batteries?

Yes. The charge profile must be configured for the exact battery or managed-BMS system rather than left on an unsuitable factory profile. Use VictronConnect or VEConfigure through a supported interface, and follow Epoch’s current charge-voltage, current-limit, temperature, and BMS-communication guidance for the battery bank.

Can I monitor and control this inverter from my phone?

Yes, with additional Victron hardware. A Cerbo GX or Ekrano GX enables system integration and VRM remote monitoring, and a VE.Bus Smart Dongle adds local Bluetooth monitoring and selected controls. An MK3-USB interface and an RJ45 UTP cable are used for computer-based configuration and firmware updates.

Can this inverter be installed outdoors or in a wet compartment?

No. The enclosure is rated IP22 and the unit must be installed in a dry, ventilated location. Do not install it in wet, dusty, explosive, or poorly ventilated spaces, and keep the clearance Victron’s manual requires around the enclosure.

More from Inverter Charger

Safety certifications & listings

Every mark below is a standard this battery has been tested against or a listing it carries. Here is what each one covers, in plain English.

  • IP22

    Ingress protection

    Objects larger than 12.5 mm, such as fingers, and protected against dripping water at up to a 15° tilt. Under IEC 60529 the first digit rates solids and the second rates water.

    • Finger-safe enclosure
    • Drips and condensation
    • Indoor installation

    IEC 60529, Degrees of protection provided by enclosures